120 kW Liquid-to-Liquid In-Rack CDU image number 0

Manfaatkan Kekuatan Air

120 kW Liquid-to-Liquid In-Rack CDU

Ikhtisar CDU In-Rack Liquid-to-Liquid Cooler Master 120 kW secara efektif mengelola beban panas rak server yang tinggi, membuang 120 kW panas dari aplikasi pusat data berkepadatan tinggi yang terus meningkat dan membutuhkan solusi in-rack. Hal ini memungkinkan pendinginan cair berkapasitas tinggi untuk pusat data guna memberikan daya dan kepadatan komputasi yang jauh lebih tinggi. CDU ini secara efektif memisahkan air fasilitas pada loop primer dan secara efisien menukar panas dari loop pendinginan IT melalui penukar panas pelat berefisiensi tinggi pada perbedaan suhu pendekatan 4°C dengan pembuangan panas 120 kW.

Features and Benefits

Features: 

  • 120 kW heat load, efficient cooling capacity.
  • 2°C to 45°C (ASHRAE W45 Liquid Cooling Class) Facility Water Supply.
  • 138 LPM maximum secondary flow rate.
  • 4.3-inch HMI Touch Screen Display.
  • 4U In-Rack chassis.
  • Integrated Command, Control, and Monitoring via TCP/IP, Modbus TCP, and Redfish.
  • Menu-Driven Controls: Status, Data Curves, Alarms, Setup, Power Consumption, Configuration, Service and Diagnostics, Sensors.
  • Alarms: Liquid Level, Liquid Leakage, High Ambient Temperature, High/Low pH Levels, High/Low Temperature, High/Low Pressure, High/Low Flow Rate.

Benefits: 

  • High in-rack heat load capacity.
  • 2,400 W power consumption.
  • Easy installation via sanitary flanges and clamps.
  • High-efficiency stainless-steel, brazed plate heat exchanger offers high heat transfer performance.
  • Condensation control via primary supply low-temperature fluid to the return bypass.
  • Ensures segregation of facility water from IT equipment, allowing the use of a variety of fluids in the secondary loop to suit specific requirements to optimize performance.
  • Precision control and monitoring of the IT equipment cooling loop.
  • Real-time fluid condition and ambient environment status, and alerts.
  • Liquid leakage detection via sensor amplifier-connected sensing cables.

 

Power, Under Control 

The Cooler Master 120 kW CDU features numerous sensors that measure flow, pressure, pH, temperature, relative humidity, and leakage, enabling accurate monitoring of fluid conditions. Operators can use CDU performance data to make actionable decisions about preventive maintenance, address potential errors or malfunctions, and receive alerts from the CDU's integrated alarm system.


120 kW CDU Control Panel Interface