CDU Cair-ke-Cair Dalam Rak 100 kW image number 0

Daya Kompak. Efisiensi Maksimal

CDU Cair-ke-Cair Dalam Rak 100 kW

Ikhtisar CDU 4U 100 kW Cooler Master secara efektif mengelola beban panas rak server yang tinggi, mendisipasi 100 kW panas dari aplikasi pusat data kepadatan tinggi yang memerlukan solusi dalam rak. Ini memungkinkan pendinginan cairan berkapasitas tinggi untuk pusat data, memberikan kepadatan daya dan komputasi yang jauh lebih tinggi. CDU secara efektif memisahkan air fasilitas di loop primer dan secara efisien menukar panas dari loop pendingin IT melalui penukar panas pelat efisiensi tinggi, mencapai perbedaan suhu pendekatan 13 °C dengan disipasi panas 100 kW.

Features and Benefits

Features: 

  • 100 kW heat load, efficient cooling capacity
  • 2°C to 45°C (ASHRAE W45 Liquid Cooling Class) Facility Water Supply
  • 85 LPM maximum secondary flow rate
  • 7-inch HMI Touch Screen Display
  • 4U In-Rack chassis
  • Integrated Command, Control, and Monitoring via TCP/IP and Modbus TCP
  • Menu-Driven Controls: Status, Data Curves, Alarms, Setup, Power consumption, Configuration, Service and Diagnostics, Sensors
  • Alarms: Liquid Level, Liquid Leakage, High Ambient Temperature, High/Low Conductivity Value, High/Low pH Levels, High/Low Temperature, High/Low Pressure, High/Low Flow Rate

Benefits: 

  • High in-rack heat load capacity.
  • 750 W power consumption.
  • Easy installation via sanitary flanges and clamps.
  • The high-efficiency stainless-steel brazed plate heat exchanger offers high heat transfer performance.
  • Condensation control via primary supply low-temperature fluid to the return bypass.
  • Ensures the segregation of facility water from IT equipment, allowing the use of various fluids in the secondary loop to meet specific requirements and optimize performance.
  • Precision control and monitoring of the IT equipment cooling loop, including pH, ORP, conductivity sensors, and filters.
  • Real-time fluid condition, ambient environment status, and alerts.
  • Liquid leakage detection via sensor amplifier-connected sensing cables.

 

Power, Under Control 

The Cooler Master 100 kW CDU features numerous sensors that measure flow, pressure, pH, ORP, conductivity, temperature, relative humidity, and leakage, enabling accurate monitoring of fluid conditions. Operators can use CDU performance data to make actionable decisions about preventive maintenance, address potential errors or malfunctions, and receive alerts from the CDU's integrated alarm system.


100 kW CDU Control Panel Interface